摘要
本次设计任务旨在体现对本专业各科知识的掌握程度,同时检验本专业的学习结果。首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。从负荷增长方面阐明了建站的必要性,然后通过对拟建变电站的概括以及出线方向来考虑,并通过对负荷资料的分析,安全,经济及可靠性方面考虑,确定了110kV,35kV,10kV的主接线,然后又通过负荷计算及供电范围确定了主变压器台数,容量及型号。最后,根据短路计算的计算结果,做出线路保护,变压器保护,母线保护。从而完成了110kV电气二次部分的设计。 关键词:电力系统,短路电流,继电保护。
ABSTRACT
Design the task this time aim at intensity of mastering of every subject knowledge of this speciality reflecting, and of test this speciality’s study result. first, analyze the tend of load department according to all parameter of load about system and circuit on task book. It expounds the necessity to this situation from the rspect of increasing load. Then through to the generalization of planning to build the transformer substation and the analysis of the load materials, safe, economy and dependability are considered, has confirmed the mainly wiring form of 110kV, 35kV, 10kV. Calculated and supplied power in the range and confirmed TV station's number of the main voltage transformer through load finally, content and type, finally, according to the result of shorting out,make the circuit to protect, the voltage transformer is protected, the bus bar is protected. Thus have finished electric designs of the part second times of 110kV. Key Words:Power system;short out the current;relay protection.
I
河南机电高等专科学校毕业设计/论文
目 录
摘要 ................................................................................................................................ Ⅰ 绪论 .................................................................................................................................. 1 第1章 变电站的分析与设计 ........................................................................................ 3 1.1变电站的总体分析 .................................................................................................... 3 1.2 变电站的负荷分析 ................................................................................................... 4 第2章 主变压器的选择及主接线选择 ........................................................................ 7 2.1 主变压器的选择 ....................................................................................................... 7 2.2 电气主接线设计 ......................................................................................................11 第3章 短路电流的计算 ............................................................................................ 17 3.1 短路的概念及路电流的种类 ................................................................................. 17 3.2 短路电流的计算 ..................................................................................................... 18 3.3 在最大运行方式下的短路电流 ............................................................................. 19 3.4 短路电流计算结果 ................................................................................................. 26 第4章 线路保护 .......................................................................................................... 27 4.1 电力系统继电保护的作用 ..................................................................................... 28 4.2 输配电线保护 ......................................................................................................... 30 4.3 线路末端短路电流 ................................................................................................. 30 4.4 线路保护整定 ......................................................................................................... 31 第5章 变压器的保护 .................................................................................................. 33 5.1 变压器的故障类型及其保护措施 ......................................................................... 33 5.2 变压器保护的整定方法 ......................................................................................... 34 5.3 变压器差动保护整定计算 ..................................................................................... 36 5.4 变压器各侧外部短路时的短路电流 ..................................................................... 37 5.5 纵差保护的整定计算 ............................................................................................. 45 第6章 母线保护 .......................................................................................................... 48 6.1 简介 ......................................................................................................................... 48 6.2 母线的保护方式 ..................................................................................................... 48 第7章 总结 .................................................................................................................. 50 致谢 ................................................................................................................................ 51 参考文献 ........................................................................................................................ 52 附录Ⅰ电气主接线图 附录Ⅱ变压器保护原理图
II
河南机电高等专科学校毕业设计/论文
附录Ⅲ 线路电流保护图
III
河南机电高等专科学校毕业设计/论文
绪论
电力工业是国民经济的一项基础工业和国民经济发展的先行工业,它是一种将煤、石油、天然气、水能、核能、风能等一次能源转换成电能这个二次能源的工业,它为国民经济的其他各部门快速、稳定发展提供足够的动力,其发展水平是反映国家经济发展水平的重要标志。
由于电能在工业及国民经济的重要性,电能的输送和分配是电能应用于这些领域不可缺少的组成部分。所以输送和分配电能是十分重要的一环。变电站使电厂或上级电站经过调整后的电能书送给下级负荷,是电能输送的核心部分。其功能运行情况、容量大小直接影响下级负荷的供电,进而影响工业生产及生活用电。若变电站系统中某一环节发生故障,系统保护环节将动作。可能造成停电等事故,给生产生活带来很大不利。因此,变电站在整个电力系统中对于保护供电的可靠性、灵敏性等指标十分重要。
变电站是联系发电厂和用户的中间环节,起着变换和分配电能的作用。这就要求变电所的一次部分经济合理,二次部分安全可靠,只有这样变电所才能正常的运行工作,为国民经济服务。
变电站是汇集电源、升降电压和分配电力场所,是联系发电厂和用户的中间环节。变电站有升压变电站和降压变电站两大类。升压变电站通常是发电厂升压站部分,紧靠发电厂。将压变电站通常远离发电厂而靠近负荷中心。这里所设计得就是110KV降压变电站。它通常有高压配电室、变压器室、低压配电室等组成。
变电站内的高压配电室、变压器室、低压配电室等都装设有各种保护装置,这些保护装置是根据下级负荷地短路、最大负荷等情况来整定配置的,因此,在发生类似故障是可根据具体情况由系统自动做出判断应跳闸保护,并且,现在的跳闸保护整定时间已经很短,在故障解除后,系统内的自动重合闸装置会迅速和闸恢复供电。这对于保护下级各负荷是十分有利的。这样不仅保护了各负荷设备的安全利于延长是使用寿命,降低设备投资,而且提高了供电的可靠性,这对于提高工农业生产效率是十分有效的。工业产品的效率提高也就意味着产品成本的降低,市场竞争力增大,进而可以使企业效益提高,为国民经济的发展做出更大的贡献。生活用电等领域的供电可靠性,可以提高人民生活质量,改善生活条件等。可见,变电站的设计是工业效率提高及国民经济发展的必然条件。
本次设计的变电站为110KV变电站,其下级负荷为35KV级乡镇企业、农业和10KV级工业及其它负荷。这些负荷不仅包括水泥厂、毛纺厂等工业部门,也有政府、市区等非工业部门。他们对供电的要求不同。依照先行的原则,依据远期负荷发展设计该变电所,本变电站主要任务是把110KV变成35kV和10kV电压供周
1
河南机电高等专科学校毕业设计/论文
边城乡使用。尤其对本地区大用户进行供电,改善提高供电水平,提高了本地供电质量和可靠性。
现在,随着大电网系统的建设,输电的电压等级越来越高,这一方面使降低损耗的需要,另一方面也是工业生产等负荷发展的需要。我国目前广泛采用的输电等级有110KV、220KV等级别,还有500KV级的输电线路也在迅速发展,所以110KV级的变电站在电力系统中的应用也十分广泛。并且伴随电力系统中所用电气元件产品诸如断路器、继电器、隔离开关等性能指标的提高,变电站的功能也会越来越完善,可靠性也会得到很大的提高。
2
河南机电高等专科学校毕业设计/论文
第1章 变电站的分析与设计
1.1变电站的总体分析
电力工业是国民经济的一项基础工业和国民经济发展的先行工业,它是一种将煤、石油、天然气、水能、核能、风能等一次能源转换成电能这个二次能源的工业,它为国民经济的其他各部门快速、稳定发展提供足够的动力,其发展水平是反映国家经济发展水平的重要标志。
随着社会的发展,电能被日益广泛的应用于工农业生产以及人民的日常生活中。电能可以方便的转化为期他形式的能源,例:机械能、热能、光能、磁能等,并且电能的输送和分配易于实现,可以输送到需要它的人和工作场所和生活场所。电能的应用规模也很灵活以电能作为动力,可以促进工农业的机械化和自动化。保证产品质量大幅度提高劳动生产率。同时提高电气化程度以电能代替其它形式的能源,是节约能源消耗的一个重要的途径。
为了满足市区生产和生活的供电要求,决定要在CZ市新建一所110KV降压变电站。变电站的站址位于CZ市东南郊,交通便利,有良好的交通运输条件,同时也为变电站职工的生活提供了方便。变电站所处区域地势平坦、土质为黏土,海拔200米,地势平坦,为非强地震区,输电线路走廊宽阔,有利于线路架设和电气设备的安装,全线为黄土层带。地耐力为2.4kgcm2,天然容重r=2gcm3,内
擦角=230,土壤电阻率为100.cm,变电所保护地下水位低,水质良好,无腐蚀性。有利于变电站的经济运行.
气象条件:年最高气温+400c,年最低气温-200c,年平均气温+150c,最热月平均最高气温+320c,最大复水厚度b=10mm,最大风速25ms,属于我国第六标准气象区。变电站选址避开了大气严重污秽和严重盐雾地区及冬季主导风向的影响,即避开了工业电力负荷,如化肥厂、纺织厂、水泥厂、柴油机厂等污染企业的影响。此外,这些电力负荷位于变电站的北部和南部,变电站设在污染源的下风口(冬季主导风向为西北风),受到轻微污染,影响电力系统的运行性能。变电站东部没有重要的电力负荷,这为进出线提供了广阔的线路走廊,还有利于变电站的扩建 ,另外,变电站选址还考虑了变电站与附近设施的影响。因此,若变电站选址不当,必将影响企业供电系统的主接线方式,电网的损失及投资的大小,还可能引起电力倒流,甚至产生更严重的后果。
3
河南机电高等专科学校毕业设计/论文
根据电力系统规划,本变电所的规模如下: 电压等级:110/35/10KV
线路回数:110KV近期2回, 远景发展2回。 35KV 近期3回, 远景发展2回 10KV 近期9回, 远景发展2回。
该变电所位于CZ市郊东南郊,交通便利,变电所的西边为10KV负荷密集区,主要有棉纺厂、食品厂、印染厂、针织厂、柴油机厂、毛纺厂及部分市区用电。变电所以东主要有35KV的水泥厂、耐火厂及市郊其它用电。
图1-1 系统接线简图
1.2 变电站的负荷分析
根据负荷允许停电程度的不同,可以将负荷分为三个等级,即一级负荷、二级负荷、三级负荷。等级不同,对电力系统供电可靠性与稳定性的要求也不同。如果停电,一级负荷将造成人身伤亡或引起对周围环境严重污染对工厂将造成经济上的巨大损失,如重要的大型的 设备损坏,重要产品或用重要原料生产的产品大量报废,还可能引起社会秩序混乱或严重的政治影响。二级负荷会造成较大的经济损失,如生产的主要设备损坏、产品大量报废或减产;还可能引起社会秩序混乱或较严重的政治影响。三级负荷造成的损失不大或不会造成直接经济损失。由此可知,供电的稳定性直接影响经济的发展,负荷等级不同,对供电的要求也不相同:对于一级负荷,必须有二个独立电源供电,且任何一个电源失去后,能保证对全部一级负荷不间断供电。对特别重要的一级负荷应该由二个独立电源点供电。对于二级负荷,一般要有两个独立电源供电,且任何一个电源失去后,能
4
河南机电高等专科学校毕业设计/论文
保证全部或大部分二级负荷供电。对于三级负荷,一般只需一个电源供电。
对于110KV侧,有市甲线、市系线,通过甲变电站、乙变电站和SI、SII相连,构成了电力系统环网。如果有任何一条线路发生故障,会直接影响电力系统环网运行的稳定性。由于各条线路的最大穿越功率不同,对电力系统造成的破坏程度也有所不同。但是,它们都会影响变电站的稳定运行,电能质量下降,导致变电 站变压器容量在三相不平衡负荷下运行,产生谐波电流,造成严重的后果。
表1—1 110kv负荷分析
电压 等级 负荷 名称 市系线 市甲线 备用1 备用2 最大负荷(MW) 负荷组成(﹪) 近期 10 10 远景 18 18 10 12 一 自然 二 力率 Tmax(H) 线长 (KM) 10 10 备注 110 kv 表1—2 35kv负荷分析
负荷 名称 水泥厂电压 1 等级 水泥厂2 耐火厂 备用1 备用2 最大负荷(MW) 负荷组成(﹪) 近期 2 2 1 远景 3 3 1.5 3 3 一 15 15 15 自然 二 力率 30 30 35 0.9 0.9 0.9 0.9 0.9 Tmax(H) 线长 (KM) 20 20 18 15 15 备注 在35KV负荷中水泥厂的一、二类负荷比较大,发生断电时,会造成生产机械的寿命缩短,产品质量下降和一定的经济损失,因此要尽可能保证其供电可靠性。
5
河南机电高等专科学校毕业设计/论文
表1-3 10KV负荷分析
负荷 名称 印染厂1 印染厂2 毛纺厂 柴油机厂1 电压 柴油机厂等级 2 橡胶厂 市区1 市区2 食品厂 备用1 备用2 最大负荷MVA 近期 1.5 1.5 2 1.5 1.5 1 1.5 1.5 1.2 2 1.5 2 2 1.5 1.5 1.5 远景 2 2 2 2 负荷组成(﹪) 一 30 30 20 25 25 30 20 20 15 二 40 40 40 40 40 40 40 40 30 自然 力率 0.78 0.78 0.75 0.8 0.8 0.72 0.8 0.8 0.8 0.78 0.78 T (H) max线长 备(KM) 注 4.5 4.5 2.5 3 3 3 2 2 1.5 5000 5000 5000 4000 4000 4500 2500 2500 4000 在10KV负荷中,印染厂、毛纺厂、柴油机厂、橡胶厂、市区一、二类负荷比较大;若发生停电对企业造成出现次品,机器损坏,甚至出现事故,对市区医院则造成不良政治和社会影响,严重时造成重大经济损失和人员伤亡,必须保证其供电可靠性。
6
河南机电高等专科学校毕业设计/论文
第2章 主变压器的选择及主接线选择
2.1 主变压器的选择 2.1.1 主变容量选择
根据“35~110KV变电所设计规范”主要变压器的台数和容量,应根据地区供电条件、负荷性质、用电容量和运行方式等条件综合考虑确定。在有一、二级负荷变电所中宜装设两台主变压器,当技术经济比较合理时,可装设两台以上主变压器。装有两台及以上主变压器的变电所,当断开一台时,其余主变压器的容量不应小于60%的全部负荷,并应保证用户的一、二级负荷。具有三种电压的变电所,如通过主变压器各侧线圈的功率均达到该变压器的15%以上,主要变压器宜采用三线圈变压器。
由于我国电力不足、缺电严重、电网电压波动较大。变压器的有载调压是改善电压质量、减少电压波动的有效手段。对电力系统,一般要求110KV及以下变电所至少采用一级有载调压变压器,因此城网变电所采用有载调压变压器的较多。 2.1.2 主变容量选择原则
(1)主变容量选择一般应按变电所建成后5-10年的规划负荷选择,并适当考虑到远期几年发展,对城郊变电所,主变容量应与城市规划相结合。
(2)根据变电所带负荷性质和电网结构来确定主变容量,对有重要负荷的变电站应考虑一台主变压器停运时,其余主变压器容量在计及过负荷能力后的允许时间内,应保证用户的一、二级负荷;对一般性变电站,当一台主变停运时,其余主变压器应能保证全部负荷的60%。
(3)同级电压的单台降压变压器容量的级别不宜太多,应从全网出发,推行系列化,标准化。
2.1.3 主变台数的选择原则
(1)对大城市郊区的一次变,在中、低压侧构成环网情况下,装两台主变为宜。
(2)对地区性孤立的一次变或大型的工业专用变电所,设计时应考虑装三台的可能性。
7
河南机电高等专科学校毕业设计/论文
(3)对规划只装两台主变的变电所,其主变基础宜大于变压器容量的1-2级设计,以便负荷发展时更换主变。
(4)在有一级,二级负荷的变电站中,应该装设两台主变电压器。当技术经济比较合理时主变压器的台数也可以多于两台。如果变电站可由中、低压侧电力网中取得足够能量的备用电源时,可以装设一台主变压器。
(5)装设两台及其以上主变压器的变电站中,当断开一台时,其余主变压器的容量应保证用户一级负荷和部分二级负荷(一般不应小于主变压器容量的60%)。具有三种电压等级的变电站中,如果通过主变压器各侧绕组的功率均达到主变压器容量的15%时,主变电压器宜采用三绕组变压器。 2.1.4 主变容量和台数选择计算
(1)35KV中压侧
其出线回路数为4回,Kt0.92,结合“1. 2变电站的负荷分析”35kv负荷情况分析表1-1知
S35kvP水泥厂1P水泥厂2P耐火厂P备用1P备用2cos(15%)kt
=
331.5330.91.050.9
=14.175MVA
SI、(S水泥厂1S水泥厂2S耐火厂)1.05kt
=(
30.90.45+
30.90.45+
1.50.90.5)1.050.9
=3.6225MVA
(2)10KV低压侧
由于其出线回路数共11回,故可取Kt=0.8,结合10kv负荷情况分析可知:
S10kvP印染厂cos1P印染厂cos2P毛纺厂cosP柴1cosP柴2cosP橡胶厂cosP市区1cosP市区2cosP食品厂cos备1Pcos备P2)
cos 8
河南机电高等专科学校毕业设计/论文
= 0.81.05(20.820.81.50.820.7820.7820.75)20.820.81.50.721.50.781.50.78
=21.5MVA
SI、(S印1S印2S毛S柴1S柴2S橡S市1S市2S备)1.05kt
=(
20.781.50.7+
20.780.7+
20.750.6+
20.80.6520.80.65
221.50.70.60.60.4)51.050.9 0.720.80.80.8=11.54MVA
则三绕组变压器的计算容量:
Sjs总2KtSjsi0.9(21.514.175)32.11MVAi1
因此,选择两台20MVA的变压器。
校验: (2-1)S选=20>S总0.6=19.27MVA
满足一台停运时另一台不小于全部容量的60%。
(2-1)S选=20>S35kv、S10kv、=15.166MVA 也满足一台停运时另一台满足全部一、二类负荷。 综上所述,最终确定为SFSZ7—20000/110型变压器。
2.1.5 绕组数和绕组连接方式的选择
参考《电力工程电气设计手册》和相应的规程中指出:在具有三种电压的变电所中,如果通过主变各绕组的功率达到该变压器容量的15%以上,或在低压侧虽没有负荷,但是在变电所的实际情况,由主变容量选择部分的计算数据,明显满足上述情况。故CZ市郊变电所主变选择三绕组变压器。
参考《电力工程电气设计手册》和相应规程指出:变压器绕组的连接方式必须和系统电压一致,否则不能并列运行。电力系统中变压器绕组采用的连接方式有Y和△型两种,而且为保证消除三次谐波的影响,必须有一个绕组是△型的,
9
河南机电高等专科学校毕业设计/论文
我国110KV及以上的电压等级均为大电流接地系统,为取得中型点,所以都需要选择Y0的连接方式。对于110KV变电所的35KV侧也采用Y0的连接方式,而6-10KV侧采用△型的连接方式。
故CZ市郊变电所主变应采用的绕组连接方式为:YN..yn0.d11。
2.1.6 全绝缘、半绝缘、绕组材料等问题的解决
在110KV及以上的中性点直接接地系统中,为了减小单相接地时的短路电流,有一部分变压器的中性点采用不接地的方式,因而需要考虑中性点绝缘的保护问题。110KV侧采用分级绝缘的经济效益比较显著,并且选用与中性点绝缘等级相当的避雷器加以保护。35KV及10KV侧为中性点不直接接地系统中的变压器,其中性点都采用全绝缘。 2.1.7 主变压器的冷却方式
根据主变压器的型号有:自然风冷式、强迫油循环风冷式、强迫油循环水冷式、强迫导向油循环式等。一般情况下,110KV变电站宜选用自然风冷式。
表2-1 SFSZ7-20000/110系列电力变压器主要技术参数
额定 容量(KVA) 额定电压(KV) 连接高 中 低 组压 压 压 别 110±38.58×± 1.25% 5% 12阻抗电压(%) 空载高低 高 中 中电流低 (%) 1.5 型号 SFSZ7-20000/110 20000 6.3 YN 6.6 17- yn0 10.5 6.5 10.5 18 d11 11 Us1%(Us12%Us31%Us23%)=10
Us2%Us3%1212(Us12%Us23%Us31%)=6
(Us23%Us31%Us12%)=0.5
10
河南机电高等专科学校毕业设计/论文
XT1US1%UN100SN2210(110)100202260.5
XT2US2%UN100SNUS3%UN100SN26(110)100200.5(110)1002036.32
XT33.0252.2 电气主接线设计
2.2.1 电气主接线的设计要求
变电所主接线设计是电力系统总体设计的组成部份。电气主接线的设计正确与否对电力系统的安全、经济运行,对电力系统的稳定和调度的灵活性,以及对电气设备的选择、配电装置的布置、继电保护及控制方式的拟定等都有重大的影响。在选择电气主接线时,应注意变电所在电力系统中的地位、作用、回路数、设备特点及负荷性质等条件,并应满足下列基本要求为:
(1)保证必要的供电可靠性和电能质量
这是电气主接线应满足的最基本要求;当系统发生故障时,要求停电范围小,恢复供电快。
(2)具有一定的运行灵活性
电气主接线不仅在正常运行情况下能根据调度要求,灵活的改变运行方式,实现安全、可靠、经济的供电;而且在系统故障或电气设备检修及故障时,能尽快的退出检修设备、切除故障,使停电时间最短,影响范围最小。
(3)操作应尽可能简单、方便
在满足必要的可靠性的前提下,主接线应简单清晰、操作方便、便于运行人员掌握。
(4)应具有扩建的可能性
随着我国国民经济的高速发展,对电力的需求也在迅速的增加。因此,在选择主接线时还要考虑到扩建的可能性。
(5)技术上先进,经济上合理
在确定主接线时,应采用先进的技术和新型的设备。同时,在保证安全可靠、运行灵活、操作方便的基础上,还应使投资和年运行费用最小、占地面积最少、经济效益最佳。
11
河南机电高等专科学校毕业设计/论文
2.2.2 主接线选择原则
电气主接线是指发电厂或变电站中的一次设备按照设计要求连接起来表示生产、汇集和分配电能的电路,也称为主电路.主接线形式于电力系统原始资料,发电厂,变电站本身运行的可靠性,灵活性和经济性的要求等密切相关,并且对电气设备的选择,配电装置布置,继电保护和控制方式的拟定都有较大的影响。
电气主接线是由高压电器通过主接线,按其功能要求组成接受和分配电能的电路,组成为传输强电流、高电压的网络,故又称为一次接线或电气主系统。主接线代表了发电厂或变电所电气部分主体结构,是电力系统的重要组成部分。它直接影响运行的可靠性、灵活性并对电器选择、配电装置布置、继电保护、自动装置和控制方式的拟定都有决定性的关系。因此,主接线的正确、合理设计,必须综合处理各方面的因素,经过技术、经济论证比较后方可确定。
对电气主接线的基本要求,概括地说应包括可靠性、灵活性和经济性三个方面。
安全可靠是电力生产的首要任务,保证供电可靠是电气主接线最基本的要求。停电不仅使发电厂造成损失,而且对国民经济各部门带来的损失将更加严重,往往比少发电能的价值大几十倍,至于导致人身伤亡、设备损坏、产品报废、城市生活混乱等经济损失和政治影响,更是难以估量。因此,主接线的接线形式必须保证供电可靠。因事故被迫中断供电的机会越少,影响范围越小,停电时间越短,主接线的可靠程度就越高。
电气主接线应能适应各种运行状态,并能灵活地进行运行方式的转换。不仅正常运行时能安全可靠地供电,而且在系统故障或电气设备检修及故障时,也能适应调度的要求,并能灵活、简便、迅速地转换运行方式,使停电时间最短,影响范围最小。因此,电气主接线必须满足调度灵活、操作方便的基本要求,既能灵活地投、切某些机组、变压器或线路,调配电源和负荷,又能满足系统在事故、检修及特殊运行方式下的调度要求,不致过多地影响对用户的供电和破坏系统的稳定运行,即具有灵活性。
在设计主接线时,主要矛盾往往发生在可靠性与经济性之间。欲使主接线可靠、灵活,必然要选用高质量的设备和现化的自动装置,从而导致投资费用的增加。因此,主接线的设计应在满足可靠性和灵活性的前提下做到经济合理。一般应当从以下几方面考虑:
(1)投资省
12
河南机电高等专科学校毕业设计/论文
主接线应简单清晰,以节省开关电器数量,降低投资;要适当采用限制短路电流的措施,以便选用价廉的电器或轻型电器;二次控制与保护方式不应过于复杂,以利于和节约二次设备及电缆的投资。
(2)占地面积少
主接线设计要为配电布置创造节约土地的条件,尽可能使占地面积减少。同时应注意节约搬迁费用、安装费用和外汇费用。对大容量发电厂或变电所,在可能和允许条件下,应采取一次设计,分期投资、投建,尽快发挥经济效益。
(3)电能损耗少
在发电厂或变电所中,正常运行时,电能损耗主要来自变压器,应经济合理地选择变压器的型式、容量、和台数,尽量避免两次变压而增加电能损耗。 2.2.3 电气主接线形式的确定
目前变电所常用的主接线形式有:单母线、单母线分段、单母线分段带旁路、双母线、双母线分段。我们在比较各种电气主接线的优劣时,主要考虑其安全可靠性、灵活性、经济性三个方面。首先,在比较主接线可靠性的时候,应从以下几个方面考虑:①断路器检修时,能否不影响供电;②线路、断路器或母线故障时以及母线或隔离开关检修时,停运出线回路数的多少和停电时间的长短,以及能否保证对重要用户的供电。其次,电气主接线应该能够适应各种运行状态,并且能够灵活地进行运行方式的切换。不仅正常时能安全可靠的供电,而且在电力系统故障或电气设备检修时,也能够适应调度的要求,并能灵活、简便、迅速地切换运行方式,使停电的时间最短,影响的范围为最小。再次,在设计变电站电气主接线时,电气主接线的优劣往往发生在可靠性与经济性之间,欲使电气主接线可靠、灵活,必然要选用高质量的电气设备和现代化的自动化装置,从而导致投资的增加。因此,电气主接线在满足可靠性与灵活性的前提下做到经济合理就可以了。
参考《35~110KV变电所设计规范》
第3.2.3条:35~110KV线路为两回及以下时,宜采用桥形线路变压器组或线路分支接线。超过两回时,宜采用扩大桥形单母线或单母分段的接线形式,35~63KV线路为8回及以上时,亦可采用双母线接线,110KV线路为6回及以上时,宜采用双母线接线。
第3.2.4条:在采用单母线、分段单母线或双母线的35~110KV主接线中,当不允许停电检修断路器时,可以设置旁路设施。
当有旁路母线时,首先宜采用分段断路器或母联断路器兼做旁路断路器的接
13
河南机电高等专科学校毕业设计/论文
线,当110KV线路为6回及以上,35~63KV线路为8回及以上时,可装设专用的旁路断路器,主变压器35~110KV回路中的断路器,有条件时,亦可接入旁路母线,采用SF6断路器的主接线不宜设旁路设施。
第3.2.5条:当变电站装有两台主变时,6~10KV侧宜采用分段单母线。线路为12回及以上时亦可采用双母线。当不允许停电检修断路器时,可设置旁路设施。
综合以上规程规定,结合本变电站的实际情况,110KV侧有4回出线(近期2回,远景发展2回),35KV侧有4回出线,10KV侧有11回出线(近期9回,远景发展2回)。故可对各电压等级侧主接线设计方案作以下处理:
(1)110kv侧
根据要求拟定下面两种接线方案。
图2-1接线图
表2-2 单母分段与单母接线比较表
方案 项目 方案I 单母分段 不会造成全部停电 调度灵活 保证对重要用户的供电 任一断路器检修,该回路必须停止工作 占地少 设备少 方案II 单母接线 技 术 经 济 简单清晰、操作方便、易于发展 可靠性、灵活性差 设备少 、投资少 综合比较方案I在经济上比方案II好,且调度灵活,可保证供电地可靠性 所以选方案I单母分段接线。 (2)35kv侧
35kv侧是本站的一个出线电压等级,它向水泥厂一、水泥厂二、耐火厂供电。这里、级所占比重比较高。对35kv侧的主接线设计了两种方案:
14
河南机电高等专科学校毕业设计/论文
图2-2接线图
表2-3 单母分段与单母接线比较表
方案 项目 方案I 单母分段 不会造成全部停电 调度灵活 保证对重要用户的供电 任一断路器检修,该回路必须停止工作 占地少 设备少 方案II 单母接线 技 术 经 济 简单清晰、操作方便、易于发展 可靠性、灵活性差 设备少 、投资少 根据本站实际情况,在35KV负荷中一、二类负荷比较大,发生断电时,会造成生产机械的寿命缩短产品质量下降和一定的经济损失.因此要尽可能保证其供电可靠性。因此选择方案Ⅰ,即单母分段接线。
(3)10kv侧
对10kv侧的主接线拟定了两种方案:
15
河南机电高等专科学校毕业设计/论文
图2-3接线图
表2-4 单母分段与双母线接线比较
方案 项目 方案I 单母分段 不会造成全部停电 调度灵活 保证对重要用户的供电 任一断路器检修,该回路必须停止工作 占地少 设备少 方案II 双母线接线 技 术 经 济 供电可靠、调度灵活、易于发展 可靠性、灵活高 设备多 、投资大 根据本站实际情况,在10KV负荷中,印染厂、毛纺厂、柴油机厂、橡胶厂、市区一、二类负荷比较大,而单母分段接线能够满足市区各级电力负荷的用电需求,考虑到随着今后经济的发展,还有扩建地可能,所以选方案II。
表2—5 主接线方案表
110kv 单母分段接线 35kv 单母分段接线 10kv 双母线接线 16
河南机电高等专科学校毕业设计/论文
第3章 短路电流的计算
3.1 短路的概念及路电流的种类 3.1.1 短路的概念
在电力系统中,短路是最常见而且对电力系统运行产生严重影响的故障。所谓短路是指相与相或相与地之间直接金属性连接。短路事故威胁着电网的正常运行中,并有可能损坏电气设备。因此,在电力系统的设计和运行中,都要对供电网络进行短路电流计算,以便正确地选用和调整继电保护装置,正确地选择电气设备,确保电力系统的安全、可靠运行。
短路的种类有以下几种: (1)三相短路。 (2)两相短路。 (3)两相短路接地。 (4)单相短路(接地)。
三相短路是对称短路,此时三相电流和三相电压仍然是对称的,只是三相电流特大。除三相短路外的其他短路都是不对称性短路,每相电流和电压数值不相等,相角也不同。 3.1.2 短路电流的危害
在供电系统中发生短路故障时,在短路回路中短路电流要比额定电流大几倍至几十倍,短路电流通过电气设备和导线必然要产生很大的电动力,并使设备温度急剧上升,可能损坏电气设备。在短路点附近电压大大降低,造成这些地方供电中断或影响电动机正常工作;发生接地短路时所出现的不对称电流,将对通信线路产生干扰;短路更严重的后果是因为电压下降可能导致电力系统发电厂之间的并列运行的稳定性遭受破坏,引起系统震荡,甚至使整个系统瓦解。 3.1.3 计算各短路电流的目的
计算短路电流的目的是为了正确选择和校验电气设备,确保设备在短路情况下不致破坏,减轻短路后果和防止故障扩大。
17
河南机电高等专科学校毕业设计/论文
计算短路电流的具体目的:
(1)选择和校验电气设备;(2)进行继电保护装置的选型与整定计算;(3)分析到电力系统的故障及稳定性能选择限制短路电流的措施;(4)确定电力线路对通信线路的影响。
ich-----短路冲击电流ich:用来校验电气设备和母线的动稳定。
Ich----短路全电流最大有效值(第一周期短路全电流有效值):用来校验电
气设备和母线的稳定。
I -----次暂态短路电流:用来作继电保护的整定计算和校验断路器的短流
量。
I-----稳态短路电流有效值:用来校验电气设备和载流部分的热稳定。 3.2 短路电流的计算
为了简化短路电流的计算方法,在保证计算精度的情况下,忽略次要因素的影响,做出一下规定:
(1) 所有的电源电动势相位角均相等,电流的频率相同,短路前,电力系统的电势和电流是对称的。
(2) 认为变压器是理想变压器,变压器的铁心始终处于不饱和状态,即电抗值不随电流的变化而变化。
(3) 输电线路的分布电容略去不计。
(4) 每一个电压级采用平均电压,这个规定在计算短路电流时,所造成的误差很小。因为电抗器的阻抗通常比其他元件阻抗大的多。
(5) 计算高压系统短路电流时,一般只计及发电机、变压器、电抗器、线路等元件的电抗,因为这些元件X/3>R时,可以略去电阻的影响。
(6) 短路点离同步调相机和同步电动机较近时,应该考虑对短路电流值的影响。有关感应电动机对电力系统三相短路冲击电流的影响:在母线附近的大容量电动机正在运行时,在母线上发生三相短路,短路点的电压立即降低。此时,电动机将变为发电机运行状态,母线上电压低于电动机的反电势。
(7) 在简化系统阻抗时,距短路点远的电源与近的电源不能合并,两个容量相差很大的电源不能够合并。
(8) 以供电电源为基准的电抗标幺值>3.5,可以认为电源容量为无限大容量的系统,短路电流的周期分量在短路全过程中保持不变。
18
河南机电高等专科学校毕业设计/论文
3.3 在最大运行方式下的短路电流
图3-1系统接线简图
将有名值转换成标幺值:
1.选择基准容量 SB=100MA 基准电压为各级电压的平均额定电压。线路电抗取X=0.4KM
线路L1:
XL1XL10.413052 线路L2:
XL2XL20.44016 线路L3:
XL3XL30.48032
X*SBL1XL1U252100B(115)20.393
X*L2XSB100L2U216B(115)20.121
X*XSB100L3L3U232(115)20.242
B X*SBT1XT1U260.5100B(115)20.457
19
河南机电高等专科学校毕业设计/论文
XT2XT2 XTXT33*SBU2B36.3100(115)20.274
SBUB23.025100(115)20.023
110kv侧简化网络图:
图3-2系统阻抗图
先将它化成星形:
图3-3系统阻抗图
将X*X****3、X*4、5化成X13、X14、X15。
**X*13X3X4X*X**0.3930.12134X50.3930.1210.2420.063
XX4X50.1210.24214XX34X0.0390.1210.2420.039
5X**X*3X50.3930.24215X***0.3930.1210.2420.126
3X4X5将X*合并成X****2、X*1323;将X1、X15合并成X25:
X***23X2X130.40.0630.463 X***25X1X150.60.1260.726
计算各电源点到短路点的转移电抗,化成△:
20
河南机电高等专科学校毕业设计/论文
图3-4系统阻抗图
X*33X*23X*14X23X14X**25***0.4630.0390.4630.0390.7260.0390.7260.4630.527
XX33为
**34X*14X*25X14X25X*230.0390.7260.826
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别应
的计算抗:
* X3X333jsS2SB0.5272001001.054
* X34X34jsS1SB0.826150010012.39
*又由于X34>3.5,故直接得I1f0Ijs1ftk2I1ftkI1f1X34js112.39
查0秒曲线得110kv侧短路电流:
If0112.39150031150.9320031151.54(KA)
查2秒曲线得110kv侧短路电流:
Iftk2112.39150031150.9420031151.55(KA)
查4秒曲线得110kv侧短路电流:
ItkIf112.3915003115120031151.61(KA)
冲击电流: ish2KMI21.81.543.92(KA) (KM取1.8) 35kv侧简化网络图:
21
河南机电高等专科学校毕业设计/论文
图3-5系统阻抗图
图3-6系统阻抗图
*X*1XT26XT220.45720.27420.366
先将它化成星形:
图3-7系统阻抗图
**X*40.12113X3XX*X*X*0.393
3450.3930.1210.2420.063XX4X50.1210.24214X0.0390.1210.2420.039
3X4X5*X*X*3X50.3930.24215X*X*34X*0.3930.1210.2420.126
5将X*******2、X*13合并成X23;将X6、X14合并成X24:将X*1、X15合并成X25:X**23X2X*130.40.0630.463
22
河南机电高等专科学校毕业设计/论文
X24X6X140.3660.0390.405 X25X1X150.60.1260.726
******计算各电源点到短路点的转移电抗,化成△:
图3-8系统阻抗图
X*33X*23X*24X23X24X**25***0.4630.4050.4630.4050.7260.4050.7260.4631.126
XX33为
**34X*24X*25X24X25X23*0.4050.7261.766
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X33jsX33* X34Xjs34*S2SBS1SB1.1262001002.25
1.766150010026.43
*又由于X34js>3.5,故直接得 I1f0I1ftk2I1ftkI1f1X34js*126.43
tk0 tk/21.5 tk3 tk时 Ijs2相等
\"\"\"I2f0I12ftk2I2ftkI2f0.465 1150337200337I26.430.4652.34(KA)
冲击电流: ish2KMI21.82.345.96(KA) (KM取1.8)
10kv侧简化网络图:
23
河南机电高等专科学校毕业设计/论文
图3-9系统阻抗图
*X*XT1X*T3620.4570.02320.24
图3-10系统阻抗图
将它化成星形:
图3-11系统阻抗图
**X*X3X40.12113X**X*0.393
3X450.3930.1210.2420.063XX4X50.1210.24214X0.0390.1210.2420.039
3X4X5*X*X*3X50.3930.24215X*X*34X*0.3930.1210.2420.126
5将X*******2、X*13合并成X23;将X6、X14合并成X24:将X*1、X15合并成X25:X**23X2X*130.40.0630.463
24
河南机电高等专科学校毕业设计/论文
X24X6X140.240.0390.279 X25X1X150.60.1260.726
******计算各电源点到短路点的转移电抗,化成△:
图3-12系统阻抗图
X*33**X*23X*24X23X24X**25*0.4630.2790.4630.2790.7260.2790.7260.4630.92
XX33为
**34X*24X*25X24X25X23*0.2790.7261.44
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X33jsX33* X3X4js34*S2SB0.922001001.84
S1SB1.44150010021.6
*又由于X34>3.5,故直接得 I1f0Ijs1ftk2I1ftkIf11X34js*121.6
查0秒曲线得10kv侧短路电流:
If0121.61500310.50.53200310.59.65(KA)
查0.5秒曲线得10kv侧短路电流:
Iftk2
200310.59.32(KA)
121.61500310.50.5查1秒曲线得10kv侧短路电流:
Iftk121.61500310.50.51200310.59.43(KA)
查曲线得10kv侧短路电流:
If121.61500310.50.58200310.510.2(KA)
冲击电流:
25
河南机电高等专科学校毕业设计/论文
ish2KMI21.89.6524K.5A 6 ((KM)取1.8) 3.4 短路电流计算结果
表3-1 短路电流计算结果表
I\"(KA) Itk(KA) II2tk(KA) I(KA) sh(KA) 110kv 1.54 1.55 1.61 1.61 3.92 35Kkv 2.34 2.34 2.34 2.34 5.96 10Kkv 9.65 9.32 9.43 10.2 24.56 26
河南机电高等专科学校毕业设计/论文
第4章 线路保护
4.1 电力系统继电保护的作用
电力系统在运行中,可能出现各种故障和不正常运行状态,员常见同时也是员危险的故障是发生各种形式的短路。在发生短路时可能产生以下的后果:
(1)通过故障点的很大的短路电流和所燃起的电弧,使故障元件损坏。 (2)短路电流通过非故障元件,由于发热和电动力的作用,引起它们的损坏或缩短它们的使用寿命。
(3)电力系统中部分地区的电压大大降低.破坏用户工作的稳定性或影响工厂产品质量。
(4)破坏电力系统并列运行的稳定性,引起系统振荡,甚至使整个系统瓦解。 故障和不正常运行状态,都可能在电力系统中引起事故。必须迅速而有选择性地切除故障元件,这是保证电力系统安全运行的最有效方法之一。切除故障的时间常常要求小到十分之几甚至百分之儿秒,实践证明只有在每个电气元件上装设一种具有“继电特性”的自动装置才有可能满足这个要求。
所谓继电保护装置,就是指能反映电力系统中电气元件发生故障d6不正常运行状态,并动作于断路器跳闸或发出信号的一种自动装置。它的基本任务是:
(1)自动、迅速、有选择性地将故障元件从电力系统中切除,使故障元件免于继续遭到破坏,保证其他无故障部公迅速恢复正常运行。
(2)反映电气元件的不正常运行状态,并根据运行维护的条件(例如有无经常值班人员)。而动作于发出信号、减负荷或跳闸。此时一般不要求保护迅速动作,而是根据对电力系统及其元件的危害程度规定一定的延时,以免不必要的动作和由于干扰而引起的误动作。
电网继电保护和安全自动装置是电力系统的重要组成部分。继电保护的装设应符合可靠性与安全性、选择性、速动形四个基本要求。设计应满足《继电保护和安全自动装置技术规程》(SDJ6—83),但针对该区域变电站其自身的特点,因此应根据电缆系统的特点制定合理的保护方案,力求做到可靠、简单、经济并适当考虑电网的发展。
电路系统的电气设备和线路应有主保护和后备保护以及必要的辅助保护。 主保护——能快速并有选择地切除被保护区域内的故障。
后备保护——在主保护或短路器拒动时,切除故障。后备保护有分为近后备保护和远后备保护两种形式:
27
河南机电高等专科学校毕业设计/论文
远后备保护是指当主保护或断路器拒动作时,由相邻设备或线路的保护实现后备。
近后备指当主保护拒动作时,由本设备或线路的另一套保护实现后备,当断路器拒动作时由断路器失灵保护实现后备。
辅助保护——当需要另还切除线路故障或消除方向功率死区时可采用由电流速断保护构成的辅助保护。
保护装置的装设原则:
1.当被保护元件发生短路或是破坏系统正常运行的情况,保护装置应动作于跳闸,当发生不正常动作时,保护装置应动作于信号。
2.为保障系统非故障部分的正常供电,保护装置应以足够小的动作时限去切除故障
3.系统故障时保护装置应有选择性地动作于跳闸,在必须加速时,可无选择性地跳闸而由自动重合闸装置来纠正保护的无选择性动作。
4.满足要求上述第二条原则或用作后备保护时,保护装置容许带有一定的时限切除故障。
5.保护装置所用的继电器越少越好,并使其接线简单可靠。
6.保护装置电压回路断线时,如可能造成保护装置的误动作则应装设电压回路断线监视或闭锁装置。
7.在表示保护装置动作的出口上应装设信号继电器。以利于运行人员分析和统计保护的动作情况。
8.主保护装置除了完成主保护任务外,如有可能还应作为相邻元件的后备保护。
9.当保护装置因动作原理不能起相邻元件的后备保护作用时,应在所有和部分断路器上装设单独的后备保护。
10.为了起到相邻元件的后备保护的作用而使保护装置复杂化,或不能达到完全的后备保护作用时,允许缩短后备范围。
11.在实际可能出现最不利的运行方式和故障类型下,保护装置应有足够的灵敏系数;
对反应电气量上升的保护装置:
灵敏系数保护范围内发生金属性短路故障参数的最小计算值保护装置的动作参数
对反应电气量下降的保护装置:
灵敏系数保护装置的动作参数保护范围内发生金属性短路故障参数的最大计算值
28
河南机电高等专科学校毕业设计/论文
各种保护装置的灵敏系数应满足电力系统《继电保护和安全自动装置技术规程》(SDJ—83)的规定。
12.保护装置的灵敏性还应该与相邻设备或线路配合。
13.保护装置所用电流互感器在最不利的条件下其误差应小于10%。 4.1.1 电力系统继电保护的基本任务
它的基本任务是:
1.当被保护的电力系统元件发生故障时,应该由该元件的继电保护装置迅速准确地给脱离故障元件最近的断路器发出跳闸命令,使故障元件及时从电力系统中断开,以最大限度地减少对电力系统元件本身的损坏,降低对电力系统安全供电的影响,并满足电力系统的某些特定要求(如保持电力系统的暂态稳定性等)。
2.反应电气设备的不正常工作情况,并根据不正常工作情况和设备运行维护条件的不同(例如有无经常值班人员)发出信号,以便值班人员进行处理,或由装置自动地进行调整,或将那些继续运行会引起事故的电气设备予以切除。反应不正常工作情况的继电保护装置允许带一定的延时动作。 4.1.2 对继电保护的基本要求
1.可靠性是指保护该动体时应可靠动作。不该动作时应可靠不动作。可靠性是对继电保护装置性能的最根本的要求。
2.选择性是指首先由故障设备或线路本身的保护切除故障,当故障设备或线路本身的保护或断路器拒动时,才允许由相邻设备保护、线路保护或断路器失灵保护切除故障。为保证对相邻设备和线路有配合要求的保护和同一保护内有配合要求的两元件(如启动与跳闸元件或闭锁与动作元件)的选择性,其灵敏系数及动作时间,在一般情况下应相互配合。
3.灵敏性是指在设备或线路的被保护范围内发生金属性短路时,保护装置应具有必要的灵敏系数,各类保护的最小灵敏系数在规程中有具体规定。继电保护的可靠性主要由配置合理、质量和技术性能优良的继电保护装置以及正常的运行维护和管理来保证。任何电力设备(线路、母线、变压器等)都不允许在无继电保护的状态下运行。220KV及以上电网的所有运行设备都必须由两套交、直流输入、输出回路相互独立,并分别控制不同断路器的继电保护装置进行保护。当任一套继电保护装置或任一组断路器拒绝动作时,能由另一套继电保护装置操作另一组断路器切除故障。在所有情况下,要求这套继电保护装置和断路器所取的直流电源
29
河南机电高等专科学校毕业设计/论文
都经由不同的熔断器供电。
4.速动性是指保护装置应尽快地切除短路故障,其目的是提高系统稳定性,减轻故障设备和线路的损坏程度,缩小故障波及范围,提高自动重合闸和备用电源或备用设备自动投入的效果等。一般从装设速动保护(如高频保护、差动保护)、充分发挥零序接地瞬时段保护及相间速断保护的作用、减少继电器固有动作时间和断路器跳闸时间等方面入手来提高速动性。 4.2 输配电线保护
设计的线路保护应满足《继电保护和全自动装置技术规程》SDJ6-83等有关专业技术规程的要求。
输电线路的主保护以动作时间上划分为全线瞬时动作及按阶梯时限特性动作两类。当要求对线路全线任何地点的任何故障均能瞬时具有选择性切除时爱用全线瞬时动作的保护作为主保护,例如各种反线路两侧电气量变化从而实现全线有选择性动作的纵联差动保护。当电网允许线路一侧以保护第二段时限切除故障时,也可采用具有阶梯时限特性的保护作为主保护,如距离保护,电流保护等。送电线路的后备保护分为远后备和近后备两类,一般采用远后备。 4.3 线路末端短路电流
35kv侧线路短路电流(选择水泥厂1的线路保护)
图4-1电流保护整定计算网络图
IK.max(3)ESXL3730.4202670(A)
(2) IK.min3ES2XL323730.4202312.5(A)
30
河南机电高等专科学校毕业设计/论文
10kv侧线路短路电流(选择毛纺厂的线路保护)
图4-2电流保护整定计算网络图
I(3)ESK.maxX10.5L30.42.56062(A)
I(2)ES10.5K3.min2X3L230.42.55250(A)
表4-1短路电流结果
35KV 10KV 最大运行 最小运行 最大运行 最小运行 2670A 2312.5A 6062A 5250A 4.4 线路保护整定
4.4.1 35kv侧线路保护整定 瞬时电流速断保护(Ⅰ段保护):
I(3)opKrelIK.max1.226703204(A)
校验: L1minX3S12EI14.44kmop0.432373.2043
LminL100%14.4420100%72.2% (满足要求)
定时限过电流保护(Ⅲ段保护):
31
河南机电高等专科学校毕业设计/论文
P3103IL.max30.95cosES30.950.93557.88(A)
IIIIKrelKSS1.21.3opKIL.max57.88106.23(A)
re0.85Krel——可靠系数,取1.2 Kest——自起动系数,取1.3
Kre——返回系数,取0.85
灵敏度校验:
(2)KK.minsenIIIII2312.5op106.2321.8﹥1.5 (满足要求)
4.4.2 10kv侧线路保护整定
瞬时电流速断保护(Ⅰ段保护):
I(3)opKrelIK.max1.260627274.4(A)
校验:
L3ES10.5min1X2I13op0.427.27431.81km
LminL100%1.812.5100%72.4% (满足要求)
定时限过电流保护(Ⅲ段保护):
3IPL.max30.95cosE210S30.950.7510162.1(A)IIIIKrelKSS1.21.3opKIL.max162.1297.5(A)
re0.85灵敏度校验:
(2)KsenIK.minIIII5250op297.517.65﹥1.5 (满足要求)
32
河南机电高等专科学校毕业设计/论文
第5章 变压器的保护
电力变压器是电力系统中非常重要的电气设备之一,它的安全运行对于保证电力系统的正常的运行和对供电的可靠性,以及电能质量起着决定性的作用。 5.1 变压器的故障类型及其保护措施 5.1.1 变压器的故障类型
变压器的内部故障可分为油箱内故障和油箱外故障,油箱内故障主要包括绕组的相间短路、匝间短路、接地短路,以及铁芯烧毁等。油箱外故障主要是套管和引出线上发生的相间短路和接地短路。电力变压器的不正常运行状态主要有外部相间短路、接地短路引起的相间过电流和零序过电流,负荷超过其额定容量引起的过负荷、油箱漏油引起的油面降低,以及过电压、过励磁等。 5.1.2 变压器装设的保护种类
为了保证变压器的安全运行,根据《继电保护与安全自动装置的运行条例》,针对变压器的故障和不正常运行状态,变压器一般装设下列继电保护装置:
1.瓦斯保护
变压器油箱内部故障和油面下降的瓦斯保护。容量为800KVA及以上的油浸式变压器,均应装设瓦斯保护。当油箱内部故障产生轻微瓦斯或油面下降时,保护装置应瞬时作用于信号;当产生大量的瓦斯时,瓦斯保护应动作于断开变压器各电源侧断路器。容量为400KVA及以上的车间内油浸式变压器,也应装设瓦斯保护。
(1) 一般气体继电器气体容积整定范围为250-300立方厘米,变压器容积在1000KVA以上时,一般正常整定为250立方厘米,气体容积整定值是利用调节重锤的位置来改变的。
(2) 重瓦斯保护油流速度的整定
重瓦斯保护动作的油流速度整定范围为0.6-1.5m/s,再整定流速均以导油管中的流速为准,而不依据继电器处的流速。
根据运行经验管中油流速整定为0.6-1.5m/s时,保护反映内部故障是相当灵敏的。但是,在变压器外部故障时,由于穿越性故障电流的影响,在导油管中油流速度约为0.4-0.5m/s。因此,为了防止穿越性故障时瓦斯保护误动作,故对本
33
河南机电高等专科学校毕业设计/论文
站的主变的瓦斯保护可将油流速度整定在1m/s左右。
2.纵联差动保护 :
反映变压器绕组和引出线相间短路及绕组匝间短路的纵联差动保护或电流速断保护。
(1) 容量为6300KVA以下的变压器,可装设电流速断保护作为变压器相间短路保护的主保护。
(2) 容量为6300KVA以上的变压器,应装设纵联差动保护作为变压器的主保护而以过电流保护作为其后备保护。
(3) 对于2000KVA以上的变压器,当电流速断保护灵敏度不能满足要求时,也应装设纵差保护。
纵差保护或电流速断保护用于反应电力变压器绕组、套管及引出线发生的短路故障,其保护动作于跳开变压器各电源侧断路器。
3.相间短路的后备保护。
过电流保护,用于降压变压器,保护装置的整定值应考虑短路时可能出现的过负荷。
复合电压(包括负序电压及线电压)启动的过电流保护。
负序电流保护和单相式低电压启动的过电流保护,用于6300KVA及以上的升压变压器。
当选择以上保护灵敏性、选择性不能满足要求时,可选择阻抗保护作后备保护。
4.接地电网中的变压器外部接地短路时的零序电流保护。110KV及以上中性直接接地电网中,如果变压器中性点接地运行,应装设反映外部接地短路的变压器零序电流保护。
5.过负荷保护。反映变压器过负荷的过负荷保护。 5.2 变压器保护的整定方法 5.2.1 变压器电流速断保护
对于2000-10000KVA及以下较小容量的变压器,可采用电流速断保护作变压器的主保护。电流速断保护装设在变压器的电源侧,当电网为中性点不直接接地系统时,电流速断保护按两相式接线;否则按三相式接线。为了提高保护对变压器高压侧因出线接地故障的灵敏系数,可采用两相三继电器式接线。
34
河南机电高等专科学校毕业设计/论文
5.2.2 变压器纵联差动保护
变压器纵联差动保护在正常运行和外部故障时,由于变压器的励磁电流、接线方式和电流互感器误差等因素的影响,使差动继电器中有不平衡电流流过,且这些不平衡电流远比发电机及线路差动保护的大。因此,减小或消除不平衡电流对差动保护的影响是变压器差动保护中很重要的问题之一。
规程中规定:对于6.3KVA及以上厂用工作变和并行运行的变压器10MVA及以上厂用备用变压器和单独运行的变压器应装设纵联差动保护,对于高压侧电压为330KV及以上变压器,可装设双重的纵联差动保护。
纵联差动保护应符合下列要求:
1.应能躲过励磁涌流和外部短路产生的不平衡电流; 2.应在变压器过励磁时不误动作;
3.差动保护范围应包括变压器套管及引出线,如不能包括引出线时,应采取快速切除故障的辅助措施。
变压器纵差保护与发电机纵差保护一样也可以采用比率制动或标记制动方式达到外部短路不误动和内部短路灵敏动作的目的。但变压器的纵差保护需考虑以下问题:
1.变压器各侧额定电压和额定电流各不相同。因此,各测电流互感器的型号、变比各不相同,所以各测电流的相位可能不一致,这样使外部短路时不平衡电流增大,所以变压器的纵差保护的最大制动系数比发电机的最大灵敏度相对较低。
2.变压器高压绕组常有调压分接头,有的甚至还要求带负荷调压,使变压器的纵差保护已调整的二次电流又被破坏,不平衡电流增大,这使变压器纵差保护的最小动作电流和制动系数都要相对增大。
3.对于定子绕组的匝间短路,发电机纵差保护完全无作用。变压器绕组各侧的匝间短路,通过变压器的铁心耦合,改变了各测电流的大小和相位,使变压器的纵差保护对匝间短路有作用(匝间短路可视为变压器的一个新绕组发生端口短路)。
4.无论变压器绕组还是发电机定子绕组开路故障,纵差保护均不能动作。变压器依靠瓦斯或压力保护来反应。变压器因为励磁电流存在,增大纵差保护的不平衡电流特别是在变压器空载投入时,励磁电流急剧增加至数十倍的额度电流,如不特别考虑将会造成纵差保护误动作。
35
河南机电高等专科学校毕业设计/论文
5.2.3 变压器后备保护
相间后备保护配置是为了防止变压器外部故障引起的过电流及作为变压器主保护的后备,变压器应装设后备保护。保护采用带低电压或不带低电压闭锁的过电流保护。如果灵敏度不够,可采用带复合电压闭锁的过电流保护。
1.对于单侧电源的变压器。后备保护装设于电源侧,作为差动保护、瓦斯保护的后备或相邻元件的后备。
2.对于多侧电源的变压器,变压器各侧均应装设后备保护; 作为变压器差动保护的后备,要求它动作后启动总出口继电器。
作为各电压侧母线和线路的后备保护,要求它动作后跳开本侧的断路器,作为变压器断路器与其电流互感器之间死区故障的后备保护。 5.2.4 变压器过负荷保护
为了防止变压器在超过允许负载能力下运行,需要装设过负荷保护装置。由于变压器的过负荷一般是三相对称的,因此,过负荷保护只需接入一项电流,各侧的过负荷保护均经过同一时间继电器延时发出信号。
保护的安装地点应能够反应变压器所有绕组的过负荷情况,对于双绕组升压变压器,过负荷保护通常装设在低压侧。对于双绕组降压变压器,过负荷保护装设在高压侧。
5.2.5 变压器过电流保护
为了防止变压器外部短路,并作为内部故障的后备保护,一般变压器上应装设过电流保护。对单侧电源的变压器,保护装置的电流互感器安装在电源侧,以便在发生变压器内部故障而瓦斯或差动保护拒动时,由过电流保护经整定时限动作后,作用于变压器两侧断路器跳闸。 5.3 变压器差动保护整定计算
计算变压器各侧的一次及二次电流值,并选择电流互感器的变比,如表所示。
36
河南机电高等专科学校毕业设计/论文
表5-1 变压器和互感器各侧电流值
名称: 额定电压: 额定电流Ie(A) CT接线方式: CT一次电流计算(A): 选用CT变比: 标准变比 CT二次额定电流Ie2(A) 182100各侧数值 110KV 200003110105 38.5KV 20000338.5300 10.5KV 20000310.51100 D 3105182 182536 d 3300520 5205104 y 1100 11005220 100 1.82 520200200 =2.6 1100300300 =3.7 所以选定10kv侧为基本侧。
5.4 变压器各侧外部短路时的短路电流 5.4.1最大运行方式下35kv侧的短路电流
35kv侧简化网络图:
图5-1系统阻抗图
37
河南机电高等专科学校毕业设计/论文
图5-2系统阻抗图
*X*T16X2XT20.457220.27420.366
先将它化成星形:
图5-3系统阻抗图
*X*X3X*413X*X*34X*0.3930.12150.3930.1210.2420.063
XX4X50.1210.24214X0.039
3X4X50.0390.1210.242X*X**3X50.3930.24215X***0.3930.1210.2420.126
3X4X5将X******2、X*13合并成X23;将X*6、X14合并成X24:将X*1、X15合并成X25:X***23X2X130.40.0630.463 X***24X6X140.3660.0390.405 X***25X1X150.60.1260.726
计算各电源点到短路点的转移电抗,化成△:
38
河南机电高等专科学校毕业设计/论文
图5-4系统阻抗图
X*33X*23X*24X23X24X**25***0.4630.4050.4630.4050.7260.4050.7260.4631.126
XX33为
**34X*24X*25X24X25X*230.4050.7261.766
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X*S233jsX33S1.126200B1002.25
X*S134jsX34S1.7661500B10026.43
由于X*1134js>3.5,故直接得 I1f0I1ftkI1ftkI1f*2X34js26.43
查曲线得35kv侧短路电流:
I126.4311503370.4652003372.34(KA)
5.4.2 最小运行方式下35kv侧的短路电流
35kv侧简化网络图:
图5-5系统阻抗图
39
河南机电高等专科学校毕业设计/论文
图5-6系统阻抗图
*X*T16X2XT20.457220.27420.366
先将它化成星形:
图5-7系统阻抗图
*X*X3X*413X*X*34X*0.3930.12150.3930.1210.2420.063
XX4X50.1210.24214X0.039
3X4X50.0390.1210.242X*X**3X50.3930.24215X***0.3930.1210.2420.126
3X4X5将X******2、X*13合并成X23;将X*6、X14合并成X24:将X*1、X15合并成X25:X***23X2X130.70.0630.763 X***24X6X140.3660.0390.405 X***25X1X150.80.1260.926
计算各电源点到短路点的转移电抗,化成△:
40
河南机电高等专科学校毕业设计/论文
图5-8系统阻抗图
X*33X*23X*24X23X24X**25***0.7630.4050.7630.4050.9260.4050.9260.7631.502
XX33为
**34X*24X*25X24X25X*230.4050.9261.823
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X*S233jsX33S1.502200B1003
X*S1150034jsX34S1.823B10027.35
由于X*134js>3.5,故直接得 I1f0II1ftk1ftkI1f12X*34js27.35
查曲线得35kv侧短路电流:
I127.3511503370.352003371.95(KA)
5.4.3 最大运行方式下10kv侧的短路电流
10kv侧简化网络图:
图5-9系统阻抗图
X*X**T1XT30.4570.0236220.24
41
河南机电高等专科学校毕业设计/论文
图5-10系统阻抗图
将它化成星形:
图5-11系统阻抗图
X*X**3X413X*X*X*0.3930.1210.063
3450.3930.1210.242XX4X50.1210.24214X0.0390.1210.2420.039
3X4X5*X*X*3X50.3930.24215X*X*34X*0.3930.1210.2420.126
5将X********2、X13合并成X23;将X*6、X14合并成X24:将X1、X15合并成X25:X***23X2X130.40.0630.463 X***24X6X140.240.0390.279 X*25X**1X150.60.1260.726
计算各电源点到短路点的转移电抗,化成△:
图5-12系统阻抗图
**X*2433X*23X*24X23XX*0.4630.2790.4630.279250.7260.92
42
河南机电高等专科学校毕业设计/论文
XX33为
**34X*24X*25X24X25X23***0.2790.7260.2790.7260.4631.44
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X33jsX33* X3X344js*S2SB0.922001001.84
S1SB1.44150010021.6
*又由于X34>3.5,故直接得 I1f0Ijs1ftk2I1ftkIf11X34js*121.6
查秒曲线得10kv侧短路电流:
If121.61500310.50.58200310.510.2(KA)
5.4.4 最小运行方式下10kv侧的短路电流:
10kv侧简化网络图:
图5-13系统阻抗图
X*6**XT1XT320.4570.02320.24
将它化成星形:
43
河南机电高等专科学校毕业设计/论文
图5-14系统阻抗图
X*13X3X4*3*4***5XXXX4X534*0.3930.1210.3930.1210.2420.1210.2420.0390.1210.2420.3930.2420.3930.1210.2420.063
X14XXXX3X5***50.039
X*15X3X4X5***0.126
*****将X2*、X1*3合并成X23;将X6*、X14合并成X24:将X1*、X15合并成X25:
X23X2X130.70.0630.763 X24X6X140.240.0390.279 X25X1X150.80.1260.926
*******计算各电源点到短路点的转移电抗,化成△:
图5-15系统阻抗图
X*33**X*23X*24X23X24X**25*0.7630.2790.7630.2790.9260.2790.9260.7631.27
XX33为
**34X*24X*25X24X25X23*0.2790.9261.54
*S2到短路点的转移电抗,X34是S1到短路点的转移电抗。它们分别对
应的计算电抗:
X33jsX33 X34jsX**S2SB1.272001002.54
S134SB1.54150010023.1
*II又由于X34js>3.5,故直接得1f01ftk2I1ftkI1f1X34js*123.1
查曲线得10kv侧短路电流:
I123.11500310.50.415200310.58.13(KA)
44
河南机电高等专科学校毕业设计/论文
5.5 纵差保护的整定计算
(1)躲过变压器励磁涌流:
Iop.calKrelIN1.311001430(A)
Krel---可靠系数,取1.3; IN--基本侧的变压器额定电流。
P10kv3U10kvcos(2)躲开电流互感器二次回路断线时变压器的最大负荷电流:
Iop.calKrelIL.max IL.max
K------可靠系数
当无法确定时,可用基本侧的额定电IL.max---变压器基本侧的最大负荷电流,流。
Iop.cal1.321033U10kvcos1.321033100.75200.2(A)
(3)躲开外部短路时的最大不平衡电流:
Iop.calKrelIunb.maxKrel(Iunb.1Iunb.2Iunb.3) Iunb.1KunpKtsferIk.max
Iunb.2UhIk.h.maxUmIk.m,maxIunb.3fer.1Ik.1.maxfer.2Ik.2.maxIk.max-----最大外部短路电流周期分量;
Krel-----可靠系数,取1.3
fer------电流互感器相对误差,取0.1; Kump--------非周期分量系数,取1.5~2;当采用速饱和变流器时,可取1。
Kts----------电流互感器的同型系数;取1;
Uh、Um------变压器高中压侧分接头改变而引起的误差,一般取调整范围的
一半;
fer.1fer.2--------继电器整定匝数与计算匝数不等引起地误差,取0.05
Iop.calKrel(KunpUhUmferKumpKst)IK.max
=1.3(110.10.050.0250.058)10200 =3090(A)
(4)确定基本侧工作线圈匝数:
45
河南机电高等专科学校毕业设计/论文
即:Ww.cal
AWoIopr.cal
其中继电器的动作电流:
Iopr.calKconIop.calnTA309030010.3(A)
AW0-----继电器动作安匝 nTA-------基本侧电流互感器变比
基本侧工作线圈匝数:
Ww.calAWoIopr.cal10010.39.7t
按继电器实际抽头,选用工作线圈匝数
Wd,setWw.cal,故选择9匝。
根据选用的基本侧工作线圈匝数,算出继电器地实际动作电流Iop.r和保护的一次动作电流Iop
实际动作电流:
Iop.rAW0Ww.set100911(A)
保护一次动作电流为:
IopIopr.calnTAKcon1130013300(A)
(5)确定非基本侧工作线圈匝数和平衡线圈匝数:
Wnb.cal.38.5IN2.bIN2.n38.5IN2.n38.5IN2.bIN2.n110IN2.n110Wd.set3.72.62.63.71.821.8293.8(t)
Wnb.cal.110Wd.set99.3(t)
所以选:
Wnb.cal.38.5Wnb.cal.11010(t)
Ww.setWd.setWb.set10919(t)
(6)整定匝数与计算匝数不等而产生的相对误差:
fer.38.5Wnb.calWnb.setWnb.calWd.set3.8103.890.480.05
46
河南机电高等专科学校毕业设计/论文
fer.110Wnb.calWnb.setWnb.calWd.set9.3109.390.0380.05
(7)灵敏系数校验:
KconIk.minIop.b132330081302.132 Ksen
由以上计算可得:DCD-2型差动继电器的插头位置在A2-B1时满足要求。
47
河南机电高等专科学校毕业设计/论文
第6章 母线保护
6.1 简介
母线是电能集中和分配的重要设备,是电力系统的重要组成元件之一。母线发生故障,将使接于母线上的所有元件被迫切除,造成大面积停电,电气设备遭到严重破坏,甚至使电力系统稳定运行破坏,导致电力系统瓦解,后果十分严重。
母线故障的原因很多,母线绝缘子和断路器套管的闪络,装与母线上的电压互感器和装在母线和断路器之间的电流互感器的故障,母线隔离开关和断路器的支持绝缘子损坏,运行人员的误操作等。
母线上发生短路故障,主要是各种类型的接地和相间短路。 6.2 母线故障的保护方式
母线故障的保护方式有两种:一种是利用供电元件的保护兼做母线保护;另一种是采用专门的母线保护。
(1) 利用变压器过流保护切除低压母线故障。
图6-1利用变压器的过电流保护切除低压母线故障
对于降压变电所低压侧采用分段单母线的系统,正常运行时QF5断开,则K点故障就可以由变压器T1的过电流保护使QF1、QF2跳闸予以切除。
48
河南机电高等专科学校毕业设计/论文
(2) 专用母线保护(完全电流差动母线保护)工作原理接线图如下:
图6-2母线完全电流差动保护原理图
在正常运行或外部故障时,流入差动继电器的电流为不平衡电流;在母线故障时,流入差动继电器的电流为故障点短路电流的二次值,该电流足够使差动继电器动作而起动出口继电器,使断路器QF1、QF2、QF3跳闸。 6.2.1 双母线同时运行时母线保护
双母线同时运行时,要求母线保护具有选择故障母线的能力。
它由三组差动保护组成。第一组由L1、L2、母联及继电器KD1组成,KD1为母线故障选择元件。KD1动作后,作用于断路器QF1、QF2跳闸。第二组由L3、L4、母联及差动继电器KD2组成。KD2为母线故障选择元件。KD2动作后,作用于QF3、QF4跳闸。第三组由L1、L4及差动继电器、KD3组成,反映两组母线上的故障,并作为整个保护的起动元件,KD3起动后作用于母联断路器QF5跳闸。保护情况说明如下:
(1)当元件固定连接方式下外部短路时,流经KD1~KD3的电流均为不平衡电流,保护装置已从整定值上躲过,故保护不会动作。元件固定连接且Ⅰ母线故障时,KD1,KD3通过短路点全部短路电流而起动,并作用于QF1,QF2,QF5跳闸,切除故障Ⅰ母线。
(2)当元件固定连接破坏后(例如Ⅰ母线上一个元件倒换到Ⅱ母线上运行),发生外部短路时,起动元件中KD3中流过不平衡电流,因此保护不会误动作。若Ⅰ母线短路,KD1,KD2,KD3都通过短路电流,它们都能起动,因此两组母线上所有断路器将跳闸,保护动作失去选择性。(这限制了母线运行的灵活性,是该保护的主要缺点)
49
河南机电高等专科学校毕业设计/论文
第7章 总结
本次变电站设计主要是电气二次部分,它主要包括变电站总体分析,主接线选择,主变选择,短路电流的计算,线路保护,变压器保护,母线保护,防雷设计等。
随着经济的发展,工业水平的进步,人们生活水平不断的提高,电力系统在整个行业中所占比例逐渐趋大。现代电力系统是一个巨大的、严密的整体。各类发电厂、变电站分工完成整个电力系统的发电、变电和配电的任务。电力系统是国民经济的重要能源部门,而变电站的设计是电力工业建设中必不可少的一个项目。由于变电站的设计内容多,范围广,逻辑性强,不同电压等级,不同类型,不同性质负荷的变电站设计时所侧重的方面是不一样的。设计过程中要针对变电站的规模和形式,具体问题具体分析。
变电站是电力系统中变换电压、接受和分配电能、控制电力的流向和调整电压的电力设施,它通过其变压器将各级电压的电网联系起来。我国电力系统的变电站大致分为四大类:升压变电站,主网变电站,二次变电站,配电站。我国电力工业的技术水平和管理水平正在逐步提高,对变电所的设计提出了更高的要求,更需要我们提高知识理解应用水平,认真对待。从我国目前部分地区用电发展趋势来看,新建变电站应充分体现出安全性、可靠性、经济性和先进性。
变电站设计的内容力求概念清楚,层次分明,结合自己设计的原始资料,参考变电站电气设计工程规范,经过大量翻阅工作,了解设计基本过程,从而进一步指导设计内容的开展。现将自己查阅文献的工作归述为:通过查阅馆藏书籍,课本和网络资源,了解电力工业的有关政策,技术规程等方面知识,理清自己的设计思路,从而为自己的设计提供有力的依据。
通过查阅文献,进行论述,提出我的设计思路和具体设计内容,以便于为设计工作提供有理可据的参考价值。通过查阅变电站设计规程,了解发变电站设计的一般过程及相关的设计规程,明白了自己要设计一个变电站的设计内容,清楚设计任务。如电气主接线设计,短路计算,继电保护,防雷接地等。树立了正确的设计思路。
本次毕业设计将是对我三年来学习的一次综合测试。通过这次设计实践工作,会使我巩固了所学知识,掌握变电所初步设计的过程。这将是对所学知识进行的一次实践,使电气专业知识得到巩固和加深,逐步提高解决问题的能力。
50
河南机电高等专科学校毕业设计/论文
致谢
经过近两个月的忙碌,本次毕业设计已经接近尾声,作为一个毕业设计,由于经验的匮乏,难免有许多考虑不周全的地方,如果没有导师的督促指导,以及同学们的支持,想要完成这个设计是很困难的。 在这里首先要感谢我的指导老师齐老师。他平日里工作繁多,但在我做毕业设计的每个阶段,从外出查阅资料,设计草案的确定和修改,中期检查,后期详细设计等整个过程中都给予了我悉心的指导。其次要感谢和我一起作毕业设计的同学,他们在本次设计中帮我解决了很多困难。最后还要感谢大学三年来所有的老师,为我们打下专业知识的基础;同时还要感谢所有的同学们,正是因为有了你们的支持和鼓励。此次毕业设计才会顺利完成。
51
河南机电高等专科学校毕业设计/论文
参考文献
[1] 范锡普.发电厂电气部分(第二版).水利电力出版社. [2] 力系统分析.水利电力出版社.
[3] 贺家李等.电力系统及电保护原理. 水利电力出版社.
[4] 水利电力部西北电力设计院.电力工程电力设计手册. 水利电力出版社. [5] 杨宛辉等. 《发电厂电气部分》设计计算资料.西北工业出版社. [6] 杨宛辉等.发电厂、变电所电气一次部分设计参考图册. [7] 电力系统继电保护与自动装置整定计算. 水利电力出版社. [8] 高电压配电装置设计技术规程SDJ5-85. 中国电力出版社. [9] 电力系统技术导则(试行)SD131-84. 中国电力出版社. [10] 电力系统设计技术规程(试行)SD131-84. 中国电力出版社. [11] 变电所总布置设计技术规定(试行)SDGJ63-84. 中国电力出版社. [12] 导体和电器选择设计技术规定SDGJ14-86. 中国电力出版社. [13] 电力设备过电压保护设计规程SDJ7-79. 水利电力出版社.
[14] 并联电容器装置设计技术规程SDJ25-85(试行). 水利电力出版社. [15] 电力设备接地设计技术规程SDJ8-97. 水利电力出版社. [16] 继电保护和安全自动装置技术规程SDJ6-83。水利电力出版社. [17] 电力勘测设计制图统一规定SDGJ34-83. 水利电力出版社.
[18] 电力设计工程电气设备手册(电气一次部分上、下). 水利电力部西北电力
设计院.
[19] 电力设计工程电气设备手册(电气二次部分). 水利电力部西北电力设计院. [20] 变电所设计(10-220KV).辽宁科学技术出版社. [21] 变电所所址选择和布置. 水利电力出版社. [22] 电网继电保护应用. 水利电力出版社.
[23] Peng you-yuan . Adjusted Design of Synchronous Generator Electric muchines &
control application,2006,33(5):7-10 [24] Yan
jian-jie,Zhao
shu-qiang,Cui
xiao-lei
.parameter
optimization
for
multi-maching power system stabilizers based on IGA. Journal of North China Electric power university, Mar.2006.Vol.33:16-20
52
因篇幅问题不能全部显示,请点此查看更多更全内容